Product Overview

This is a liquid oxygen scavenger, typically based on catalysed sodium sulfite, which reacts with the dissolved oxygen left after deaeration. A catalyst speeds up the reaction, which matters when feedwater is cool or contact time is short. It comes in a standard strength for small and medium boilers and a stronger version for larger boilers with higher feed rates.

Feed it continuously to the deaerator storage section or feed tank. Low- and medium-pressure boilers usually keep a sulfite residual above about 20 ppm. Sulfite adds dissolved solids, so it should not go into water used for attemperation, and high-pressure units may need a volatile scavenger instead.

Applications

Steam boilers — removing residual dissolved oxygen
Feed tanks and deaerators — preventing oxygen pitting
Economisers — protecting tubes where feed is cooler
Boiler wet lay-up — keeping stored boilers oxygen-free