LX-WTP-001Oxygen Scavenger — Standard & Big Boiler
At a glance
- Typical use
- Removing dissolved oxygen from boiler feedwater to stop pitting corrosion
- Category
- Boiler Water Treatment
- Product code
- LX-WTP-003
- Availability
- Available on Request
Share your quantity, grade and delivery location. Our desk confirms make, specification, packaging and lead time in writing, typically within one business day.
Product Overview
This is a liquid oxygen scavenger, typically based on catalysed sodium sulfite, which reacts with the dissolved oxygen left after deaeration. A catalyst speeds up the reaction, which matters when feedwater is cool or contact time is short. It comes in a standard strength for small and medium boilers and a stronger version for larger boilers with higher feed rates.
Feed it continuously to the deaerator storage section or feed tank. Low- and medium-pressure boilers usually keep a sulfite residual above about 20 ppm. Sulfite adds dissolved solids, so it should not go into water used for attemperation, and high-pressure units may need a volatile scavenger instead.