LX-WTP-024RO Biocide
At a glance
- Typical use
- Controlling biofouling in RO membranes and pretreatment without chlorine damage
- Category
- RO Plant Chemicals
- Product code
- LX-WTP-025
- Availability
- Available on Request
Share your quantity, grade and delivery location. Our desk confirms make, specification, packaging and lead time in writing, typically within one business day.
Product Overview
RO Biocide is a non-oxidising biocide for reverse osmosis systems, usually based on DBNPA (dibromonitrilopropionamide). Polyamide thin-film membranes are damaged by free chlorine, so a non-oxidising product is used to control bacteria and the biofilm that raises differential pressure and lowers flux. DBNPA acts fast and breaks down in water into less harmful products.
It is slug-dosed into the RO feed, intermittently or during cleaning and lay-up. The permeate from dosing periods is usually sent to drain in potable or food plants. Check membrane-maker compatibility, and handle the concentrate with gloves and eye protection.