LX-WTP-014Multifunctional Cooling Treatment — Soft Water / Raw Water
One-product scale, corrosion and deposit control for open cooling towers
Share your quantity, grade and delivery location. Our desk confirms make, specification, packaging and lead time in writing, typically within one business day.
Cooling Water Anti-Corrosion Treatment is a liquid inhibitor blend for open and closed cooling circuits. Typical actives include orthophosphate and molybdate, which passivate steel at anodic sites, and zinc, which precipitates a film at cathodic sites. Azoles such as tolyltriazole are added to protect copper and brass. Nitrite-based grades are common for closed loops.
It is used where soft, low-pH or high-chloride water attacks carbon steel heat exchangers and pipework. Dose it continuously against make-up or blowdown, and check inhibitor residual and corrosion coupons. Excess chlorination deactivates azoles, so coordinate the dose with the biocide programme.