Water Treatment Programme Chemicals

Dispersant

Dispersant — Cooling Tower Treatment
Cooling Tower TreatmentLX-WTP-017

At a glance

Typical use
Keeping silt, iron oxide and suspended solids dispersed in cooling water
Product code
LX-WTP-017
Availability
Available on Request
Request a quote

Share your quantity, grade and delivery location. Our desk confirms make, specification, packaging and lead time in writing, typically within one business day.

Talk to Sales

Product Overview

This cooling water dispersant is a liquid based on low-molecular-weight anionic polymers, usually acrylate types. It adsorbs onto fine particles of silt, clay, iron oxide and precipitated salts and adds to their negative charge. The particles then repel each other and stay suspended, instead of agglomerating and settling as sludge in heat exchangers and tower basins.

It is used where make-up water carries suspended solids, where airborne dust enters the tower, or where corrosion products build up. The dispersed solids leave with blowdown and side-stream filtration. It is often fed together with scale and corrosion inhibitors, in proportion to blowdown.

Applications

Cooling towers — preventing silt and sludge deposits
Heat exchangers — reducing particulate fouling
Iron control — keeping iron oxides suspended
Side-stream filtration — helping solids reach the filter