Water Treatment Programme Chemicals

Volatile Amine Treatment

Volatile Amine Treatment — Boiler Water Treatment
Boiler Water TreatmentLX-WTP-009

At a glance

Typical use
Neutralising carbonic acid to stop corrosion in steam and condensate lines
Product code
LX-WTP-009
Availability
Available on Request
Request a quote

Share your quantity, grade and delivery location. Our desk confirms make, specification, packaging and lead time in writing, typically within one business day.

Talk to Sales

Product Overview

Volatile Amine Treatment is a neutralising amine blend, typically based on morpholine, cyclohexylamine or diethylaminoethanol (DEAE). The amines vaporise with the steam and condense with it, where they neutralise the carbonic acid formed by carbon dioxide. Carbonic acid is the main cause of low condensate pH and the grooving corrosion it causes in return lines.

It is used in process steam systems with long condensate networks. The blend is chosen by distribution ratio, so that amine reaches both early and late condensation points. Condensate in mixed copper and iron systems is often held near pH 8.8–9.2. Feed it to the feedwater or steam header and check condensate pH regularly.

Applications

Condensate lines — raising pH to stop carbonic acid attack
Steam distribution — protecting headers, traps and returns
Heat exchangers — reducing iron and copper pickup
Feedwater — pH control without adding dissolved solids